Tool · Electrical
Three-Phase Power Calculator
How many kW can a 16 A three-phase supply carry, how much current does an 11 kW charger draw? Enter two of voltage, current and power – the tool works out the rest, for single-phase 230 V and three-phase 400 V, with power factor, apparent and reactive power.
From this tool on Amazon: Clamp meter*
Marked with *: affiliate links. As an Amazon Associate I earn from qualifying purchases.What you need it for
- What can a supply carry? A 16 A industrial socket or a 32 A breaker – how much power is that on three-phase?
- What current flows? The rating plate gives the power and you want the current in each line, for example to choose the protective device or the cable.
- Motors and power supplies: with a power factor below 1, the apparent power is larger than the real power – it matters for generators, inverters and UPS units rated in kVA.
- Learning: the working shows every formula with the numbers filled in – for exams and college.
The formulas
V is the voltage, I the current and φ the angle by which the current lags (or leads) the voltage. On three-phase, V is the line-to-line voltage between two lines and I the current in one line:
| Quantity | Single-phase 1~ | Three-phase 3~ | Unit |
|---|---|---|---|
| Apparent power | S = V · I | S = √3 · V · I | VA |
| Real power | P = V · I · cos φ | P = √3 · V · I · cos φ | W |
| Reactive power | Q = V · I · sin φ | Q = √3 · V · I · sin φ | var |
| Current from power | I = P ÷ (V · cos φ) | I = P ÷ (√3 · V · cos φ) | A |
The formulas hold when the load is shared equally between the three lines and there are no harmonics. In addition, S² = P² + Q² and cos φ = P ÷ S always apply.
Where the √3 comes from: on a 230/400 V supply there are 230 V between each line and neutral and √3 · 230 V ≈ 400 V between two lines. Three phases with 230 V and 16 A each give 3 · 230 V · 16 A = 11.04 kVA – written with the line-to-line voltage, √3 · 400 V · 16 A ≈ 11.09 kVA. It is the same formula; the small difference is because 400 V is rounded to whole volts (exactly it would be 398.4 V).
Real, apparent and reactive power
- Real power P in watts becomes heat, light or motion. It is what the electricity meter counts.
- Reactive power Q in var flows back and forth between supply and load, for example to build up the magnetic field of a motor. It does no work, but it loads cables and generators.
- Apparent power S in VA is what the cable actually carries: voltage times current. Cable size, protective device and the size of a transformer or generator depend on it.
The three form a right-angled triangle, the power triangle. cos φ, the displacement factor, tells you which share of the apparent power is real power. For an immersion heater, kettle or filament lamp, cos φ = 1: P and S are equal and Q is zero.
Worked examples
Example 1: 16 A three-phase – how many kW?
A 16 A industrial socket on 400 V, load with cos φ = 1 – these values are in the calculator when it opens:
- S = √3 · 400 V · 16 A ≈ 11.09 kVA
- P = S · cos φ = 11.09 kVA · 1 = 11.09 kW
On single-phase at 230 V, 16 A gives only 230 V · 16 A = 3.68 kW – for the same current per conductor, three-phase carries about three times as much.
Example 2: current of an 11 kW EV charger
A charger delivers 11 kW on three phases, assuming cos φ = 1:
- I = P ÷ (√3 · V · cos φ) = 11,000 W ÷ (√3 · 400 V · 1) ≈ 15.88 A per line
That is why 11 kW goes with a 16 A protective device.
Example 3: three-phase motor with cos φ = 0.82
A motor’s rating plate shows 400 V, 13.5 A and cos φ = 0.82 (example values):
- S = √3 · 400 V · 13.5 A ≈ 9.35 kVA
- P = S · cos φ = 9.35 kVA · 0.82 ≈ 7.67 kW real power drawn
- sin φ = √(1 − 0.82²) ≈ 0.5724, so Q = S · sin φ ≈ 5.35 kvar
The kW figure on a motor’s rating plate is the output power at the shaft. The real power drawn is larger by the losses; the ratio of the two is the efficiency. For current and cable sizing, use the rated current from the plate, not the shaft power.
The calculator is tested against all three examples.
Power per protective device: 10 to 63 A
The most power that flows at common breaker ratings, every cell worked out with the calculator: current equal to the rated current of the device, cos φ = 1, so real power in kW equals apparent power in kVA. With a power factor below 1, the real power is lower accordingly.
| Rating | Single-phase 230 V | Three-phase 400 V |
|---|---|---|
| 10 A | 2.30 kW | 6.93 kW |
| 13 A | 2.99 kW | 9.01 kW |
| 16 A | 3.68 kW | 11.09 kW |
| 20 A | 4.60 kW | 13.86 kW |
| 25 A | 5.75 kW | 17.32 kW |
| 32 A | 7.36 kW | 22.17 kW |
| 63 A | 14.49 kW | 43.65 kW |
This is the arithmetic limit. Protective device and cable have to match, and not every installation is meant to run continuously at rated current.
The other way round: what current flows at a given power? Again cos φ = 1, rounded to two decimal places:
| Power | Single-phase 230 V | Three-phase 400 V |
|---|---|---|
| 1 kW | 4.35 A | 1.44 A |
| 2 kW | 8.70 A | 2.89 A |
| 3 kW | 13.04 A | 4.33 A |
| 4.6 kW | 20.00 A | 6.64 A |
| 7.5 kW | 32.61 A | 10.83 A |
| 11 kW | 47.83 A | 15.88 A |
| 15 kW | 65.22 A | 21.65 A |
| 22 kW | 95.65 A | 31.75 A |
Checking the current with a clamp meter
Whether a load really draws the current you worked out is shown by a clamp meter. It goes round a single conductor and measures the current without breaking the circuit. On three-phase, measure each line separately; if the three readings are far apart, the load is unbalanced and the formulas above are only approximate. Clamped round a whole cable with line and neutral, it reads almost zero – the currents cancel out. For AC the clamp must measure AC; for measurements in a distribution board it needs the right measurement category (CAT), and work there is for a qualified electrician.
Next: cable and voltage drop
The current from this calculator is the starting point for sizing the circuit. The Kabelberechnung (cable sizing) and the Spannungsfall-Rechner (voltage drop) work to the German DIN VDE standards and are available in German only. For DC and purely resistive loads without a power factor, the Ohm’s law calculator is enough.
Limits of this tool
- Balanced load: three-phase is worked out with the same current in all three lines. For an unbalanced load, work out each phase separately as single-phase against 230 V.
- No harmonics: power supplies, LED drivers and variable speed drives do not draw a sinusoidal current. The power factor is then no longer equal to cos φ, and the formulas are only approximate.
- Reactive power as magnitude: the tool does not distinguish between inductive (motor) and capacitive.
- No check of cable, protective device or supply capacity.
- The result is a calculation aid. Responsibility for design and installation stays with the qualified electrician.
Privacy: the calculator runs entirely in your browser. Your entries are not sent to xmoo.app or anyone else.
Sources
- Apparent power S = √3 · V · I, real power P = √3 · V · I · cos φ, reactive power Q = √3 · V · I · sin φ (balanced, without harmonics), line-to-line voltage = √3 · phase voltage, single-phase P = V · I · cos φ and Q = V · I · sin φ: Valentin Crastan, Elektrische Energieversorgung 1, 4th edition, Springer Vieweg 2015, ISBN 978-3-662-45984-3, section 2.1.4, equations (2.1) to (2.3) (sample chapter 2, in German); current from power, S² = P² + Q² and cos φ = P ÷ S rearranged from these
- Nominal voltage 230/400 V according to EN 60038: VDE-AR-N 4100:2026-04 (German technical connection rules for the low-voltage grid), section 5.1
Page last updated: 16 November 2026