Three-Phase Power Calculator

How many kW can a 16 A three-phase supply carry, how much current does an 11 kW charger draw? Enter two of voltage, current and power – the tool works out the rest, for single-phase 230 V and three-phase 400 V, with power factor, apparent and reactive power.

Supply

Three-phase: line-to-line voltage (400 V); single-phase: 230 V.

Three-phase: current in each line.

kW and W: real power, kVA and VA: apparent power.

1 for heaters and kettles, for motors from the rating plate.

Fill in exactly two of voltage, current and power.

Real power P
Apparent power S
Reactive power Q
Current I
Voltage V
Power factor

      

From this tool on Amazon: Clamp meter*

Marked with *: affiliate links. As an Amazon Associate I earn from qualifying purchases.

What you need it for

The formulas

V is the voltage, I the current and φ the angle by which the current lags (or leads) the voltage. On three-phase, V is the line-to-line voltage between two lines and I the current in one line:

QuantitySingle-phase 1~Three-phase 3~Unit
Apparent powerS = V · IS = √3 · V · IVA
Real powerP = V · I · cos φP = √3 · V · I · cos φW
Reactive powerQ = V · I · sin φQ = √3 · V · I · sin φvar
Current from powerI = P ÷ (V · cos φ)I = P ÷ (√3 · V · cos φ)A

The formulas hold when the load is shared equally between the three lines and there are no harmonics. In addition, S² = P² + Q² and cos φ = P ÷ S always apply.

Where the √3 comes from: on a 230/400 V supply there are 230 V between each line and neutral and √3 · 230 V ≈ 400 V between two lines. Three phases with 230 V and 16 A each give 3 · 230 V · 16 A = 11.04 kVA – written with the line-to-line voltage, √3 · 400 V · 16 A ≈ 11.09 kVA. It is the same formula; the small difference is because 400 V is rounded to whole volts (exactly it would be 398.4 V).

Real, apparent and reactive power

The three form a right-angled triangle, the power triangle. cos φ, the displacement factor, tells you which share of the apparent power is real power. For an immersion heater, kettle or filament lamp, cos φ = 1: P and S are equal and Q is zero.

φ = 34.9° P = 7.67 kW real power Q = 5.35 kvar reactive power S = 9.35 kVA apparent power S = √3 · 400 V · 13.5 A ≈ 9.35 kVA P = S · 0.82 ≈ 7.67 kW
Power triangle of the motor in example 3: real and reactive power are at right angles, the apparent power is the hypotenuse. cos φ = P ÷ S = 0.82. Own illustration.

Worked examples

Example 1: 16 A three-phase – how many kW?

A 16 A industrial socket on 400 V, load with cos φ = 1 – these values are in the calculator when it opens:

  1. S = √3 · 400 V · 16 A ≈ 11.09 kVA
  2. P = S · cos φ = 11.09 kVA · 1 = 11.09 kW

On single-phase at 230 V, 16 A gives only 230 V · 16 A = 3.68 kW – for the same current per conductor, three-phase carries about three times as much.

Example 2: current of an 11 kW EV charger

A charger delivers 11 kW on three phases, assuming cos φ = 1:

  1. I = P ÷ (√3 · V · cos φ) = 11,000 W ÷ (√3 · 400 V · 1) ≈ 15.88 A per line

That is why 11 kW goes with a 16 A protective device.

Example 3: three-phase motor with cos φ = 0.82

A motor’s rating plate shows 400 V, 13.5 A and cos φ = 0.82 (example values):

  1. S = √3 · 400 V · 13.5 A ≈ 9.35 kVA
  2. P = S · cos φ = 9.35 kVA · 0.82 ≈ 7.67 kW real power drawn
  3. sin φ = √(1 − 0.82²) ≈ 0.5724, so Q = S · sin φ ≈ 5.35 kvar

The kW figure on a motor’s rating plate is the output power at the shaft. The real power drawn is larger by the losses; the ratio of the two is the efficiency. For current and cable sizing, use the rated current from the plate, not the shaft power.

The calculator is tested against all three examples.

Power per protective device: 10 to 63 A

The most power that flows at common breaker ratings, every cell worked out with the calculator: current equal to the rated current of the device, cos φ = 1, so real power in kW equals apparent power in kVA. With a power factor below 1, the real power is lower accordingly.

Power at rated current, cos φ = 1
RatingSingle-phase 230 VThree-phase 400 V
10 A2.30 kW6.93 kW
13 A2.99 kW9.01 kW
16 A3.68 kW11.09 kW
20 A4.60 kW13.86 kW
25 A5.75 kW17.32 kW
32 A7.36 kW22.17 kW
63 A14.49 kW43.65 kW

This is the arithmetic limit. Protective device and cable have to match, and not every installation is meant to run continuously at rated current.

The other way round: what current flows at a given power? Again cos φ = 1, rounded to two decimal places:

Current per conductor at a given real power, cos φ = 1
PowerSingle-phase 230 VThree-phase 400 V
1 kW4.35 A1.44 A
2 kW8.70 A2.89 A
3 kW13.04 A4.33 A
4.6 kW20.00 A6.64 A
7.5 kW32.61 A10.83 A
11 kW47.83 A15.88 A
15 kW65.22 A21.65 A
22 kW95.65 A31.75 A

Checking the current with a clamp meter

Whether a load really draws the current you worked out is shown by a clamp meter. It goes round a single conductor and measures the current without breaking the circuit. On three-phase, measure each line separately; if the three readings are far apart, the load is unbalanced and the formulas above are only approximate. Clamped round a whole cable with line and neutral, it reads almost zero – the currents cancel out. For AC the clamp must measure AC; for measurements in a distribution board it needs the right measurement category (CAT), and work there is for a qualified electrician.

AC clamp meter*

Marked with *: affiliate links. As an Amazon Associate I earn from qualifying purchases.

Next: cable and voltage drop

The current from this calculator is the starting point for sizing the circuit. The Kabelberechnung (cable sizing) and the Spannungsfall-Rechner (voltage drop) work to the German DIN VDE standards and are available in German only. For DC and purely resistive loads without a power factor, the Ohm’s law calculator is enough.