xmoo Cable Sizing API

Size low-voltage cables to IEC 60364 and DIN VDE 0298-4 in one request – cross-section, protective device, voltage drop, automatic disconnection and short-circuit withstand, with the formula and values behind every step.

What it does

Each answer names the standard, table and column it used, and lists the calculation step by step in plain text – ready to show to your users or to put into a report. Nothing is stored. It is the same engine as the free cable sizing tool on this site (in German).

Standards

Current-carrying capacities and correction factors come from DIN VDE 0298-4:2023-06 (Tables 3–6, 17, 20–26, 29). Its values are those of HD 60364-5-52 / IEC 60364-5-52 Annex B, so the API fits every country that uses these tables. The calculation follows IEC 60364-4-43 (overload protection), IEC 60364-5-52 (voltage drop, resistive part) and IEC 60364-4-41 (automatic disconnection) with the minimum single-phase fault current to IEC 60909-0 (cmin = 0.9, conductor at its permissible short-circuit temperature). Supply voltages are 230 V / 400 V.

The API is a planning aid without warranty. It replaces neither professional design nor verification to IEC 60364-6. National deviations from these tables are not covered – check the rules that apply where you install.

Access

The API is offered through RapidAPI, where you subscribe to a plan, get your key and the host name for your requests. The listing is being prepared – the link will appear here as soon as it is live. Questions: julian@haag-automation.com.

All endpoints take and return JSON (Content-Type: application/json, body up to 64 KB). The examples expect your key and host in RAPIDAPI_KEY and RAPIDAPI_HOST.

Endpoints

EndpointPurpose
POST /v1/electrical/cable/sizeSize a cable and its protective device, all checks
POST /v1/electrical/current-capacityCurrent-carrying capacity Ir and Iz for one installation
POST /v1/electrical/voltage-dropVoltage drop, longest length, smallest cross-section
GET /v1/electrical/tablesAllowed values: installation methods, groupings, temperatures, devices, cross-sections

Field descriptions: api.xmoo.app/electrical/openapi.json (OpenAPI 3.0). Descriptive texts are English; lang=de returns German.

Examples

Real answers of the API, shortened where marked. A test on our side sends these requests and checks that the answers still match.

Size a sub-distribution feeder

50 kW three-phase at cos φ 0.95, 30 m, installation method C, 35 °C, gG fuse, distribution circuit, 100 mΩ fault loop impedance up to the origin of the circuit:

curl -s -X POST "https://$RAPIDAPI_HOST/v1/electrical/cable/size" \
  -H "x-rapidapi-key: $RAPIDAPI_KEY" \
  -H "x-rapidapi-host: $RAPIDAPI_HOST" \
  -H "Content-Type: application/json" \
  -d @request.json
{
  "supply": "three-phase",
  "power": 50000,
  "powerFactor": 0.95,
  "length": 30,
  "installationMethod": "C",
  "ambientTemperature": 35,
  "protectiveDevice": "gG",
  "circuitType": "distribution",
  "upstreamImpedance": 100
}

Answer, shortened to the main results and the first of six steps:

{
  "status": "ok",
  "result": {
    "designCurrent": 75.97,
    "protectiveDevice": {
      "type": "gG",
      "ratedCurrent": 80,
      "conventionalCurrentI2": 128
    },
    "requiredCurrentCapacity": 88.28,
    "crossSection": 25,
    "tabulatedCapacity": 96,
    "currentCapacity": 90.24,
    "factors": {
      "temperature": 0.94,
      "grouping": 1
    },
    "voltageDrop": {
      "volts": 2.68,
      "percent": 0.67,
      "ok": true
    },
    "disconnection": {
      "maxTime": 5,
      "disconnectionCurrent": 440,
      "loopImpedance": 0.1669,
      "minShortCircuitCurrent": 1240.58,
      "ok": true
    },
    "shortCircuit": {
      "k": 115,
      "permissibleTime": 5.37,
      "ok": true
    },
    "recommendation": {
      "text": "NYM-J 5×25 mm², 3 × gG 80 A (e.g. NEOZED D03 or NH size 000/00)"
    }
  },
  "sources": {
    "standard": "DIN VDE 0298-4:2023-06",
    "table": "Table 3",
    "hd60364552": "B.52.4/6"
  },
  "steps": [
    {
      "step": 1,
      "title": "Design current Ib",
      "standard": null,
      "status": "ok",
      "lines": [
        "Ib = P ÷ (√3 × U × cos φ) = 50,000 W ÷ (1.732 × 400 V × 0.95) = 75.97 A"
      ],
      "nextStep": null
    }
  ],
  "notice": "Planning aid without warranty; it replaces neither professional design nor verification to IEC 60364-6."
}

status is ok when every check passes, failed when a condition is not met (the step then says what to do in nextStep), incomplete when a step could not be checked – for example without upstreamImpedance – and note when the short-circuit check needs a manufacturer value.

Voltage drop of a final circuit

16 A single-phase, 25 m, 1.5 mm² copper:

{
  "supply": "single-phase",
  "current": 16,
  "length": 25,
  "crossSection": 1.5
}
{
  "designCurrent": 16,
  "voltage": 230,
  "conductivity": 56,
  "voltageDrop": {
    "volts": 9.52,
    "percent": 4.14,
    "ok": false
  },
  "maxLength": 24.15,
  "smallestCrossSectionWithinLimit": {
    "crossSection": 2.5,
    "volts": 5.71,
    "percent": 2.48
  },
  "formula": "ΔU = 2 × L × I × cos φ ÷ (κ × A)",
  "note": "Resistive part only, conductor at 20 °C; the inductive reactance of large cross-sections is not included."
}

4.14 % is above the default limit of 4 %: the cable may be at most 24.15 m long, or 2.5 mm² keeps the drop at 2.48 %.

Which cross-section carries 32 A?

Installation method B2, three loaded conductors, 40 °C ambient:

{
  "installationMethod": "B2",
  "loadedConductors": 3,
  "ambientTemperature": 40,
  "requiredCurrent": 32
}

Answer, shortened to the first three cross-sections of the list:

{
  "conductor": "copper",
  "insulation": "pvc-70",
  "column": {
    "installationMethod": "B2",
    "loadedConductors": 3,
    "arrangement": null
  },
  "factors": {
    "temperature": 0.87,
    "grouping": 1,
    "soil": null,
    "groupingCircuitsInTable": 1,
    "total": 0.87
  },
  "smallestSufficient": {
    "crossSection": 10,
    "tabulatedCapacity": 46,
    "currentCapacity": 40.02
  },
  "capacities": [
    {
      "crossSection": 1.5,
      "tabulatedCapacity": 15,
      "currentCapacity": 13.05
    },
    {
      "crossSection": 2.5,
      "tabulatedCapacity": 20,
      "currentCapacity": 17.4
    },
    {
      "crossSection": 4,
      "tabulatedCapacity": 27,
      "currentCapacity": 23.49
    }
  ],
  "sources": {
    "standard": "DIN VDE 0298-4:2023-06",
    "table": "Table 3",
    "hd60364552": "B.52.4/5",
    "factors": [
      "Table 17",
      "Table 22"
    ]
  }
}

Errors

Errors come as JSON with a code, a message and, for input errors, the field:

{
  "error": {
    "code": "missing_field",
    "message": "\"crossSection\" is required.",
    "field": "crossSection"
  }
}
StatusCodeMeaning
400bad_json, invalid_langBody is not a JSON object, unknown language
401unauthorizedRequest did not come through RapidAPI
404, 405not_found, method_not_allowedUnknown endpoint or wrong HTTP method
413too_largeBody larger than 64 KB
415unsupported_media_typeBody is not sent as application/json
422missing_field, invalid_field, invalid_inputA required field is missing or a value is outside the tables – see field